March 6, 1968

away. After 10 minutes the temperature dropped 1°F
to 49°. The chiller vanes are still almost closed. We
1145 are now putting a recording thermometer on the chiller
water manifold in the disk. The water flow is now
2 gal/min. The automatic flow valve appears to be
almost closed.

1200 The chiller thermostat has been changed from 50°F
to 55°F. We will keep an eye on the temp. recorder. If
the chiller water temp. is drifting, we should call
the chiller repair service to check it. Meanwhile the
chiller water temp. is considerably below the 70°F -
Electronics turn off temperature, so there is no reason
why we can use the disk. THe electronics was turned
on at about 1030 and has been operating on read
only without errors (Inhibit Read Compare is on.).
J. Gleason

Mar 6, 68 14:20

Complaints from 2 people [?] 8981 that
they can not take [?] computer (bad cord?)
spcwar button 30 sticks on
[N.S.N?]

1440
Found that the 8981 plug was not plugged
all the way in.
J. Gleason

Have just picked up our Triplet meter which
has been repaired and calibrated. Also picked up
the 1A1 Plug-in which was also repaired and calibrated.
J. Gleason